 [XM6168]  Ultraviolet lamp intensity detection sensor

Technical parameterParameter value
BrandXUNCHIP
measurement rangemax is 0~400mW/cm2(4/10/100/200 can selected)
measurement accuracy ± 7% FS
wavelength range UVA/UVB/UVC
Maximum angle 90 degrees
Reso InterfaceRS485/4-20mA/DC0-10V

Product Selection

    Product DesignRS485,4-20mA,DC0-10VMultiple output methods, the products are divided into the following models depending on the output method.
Product model output method
XM6168BRS485总线
XM6168M4-20mA
XM6168V10DC0-10V

Communication Protocol

    The product uses RS485 MODBUS-RTU standard protocol format, all operation or reply commands are hexadecimal data. The default device address is 1 when the device leaves the factory, and the module or NON-Recorder default baud rate is 9600,8,n,1 ,but data recorder default baud rate is 115200 .
1. Read data (function code 0x03)
    Inquiry frame (hexadecimal), sending example: query 1 data of 1# device, the upper computer sends the command: 01 03 00 00 00 01 84 0A .
Address Function Code Start Address Data Length Check Code
010300 0000 0184 0A
    For the correct query frame, the device will respond with data: 01 03 02 00 79 79 A6 , response format:
Address Function Code LengthData 1Check Code
0103 0200 79 79 A6
    Data description: The data in the command is hexadecimal, take data 1 as an example, 00 79 is converted to decimal value as 121, assuming the data magnification is 100, then the real value is 121/100=1.21, Others and so on.
2. Common data address table
Configuration Address Register Address Register Description Data Type Value Range
4000100 00大量程紫外线Read Only0~65535
4010100 64Model CodeRead/Write0~65535
4010200 65 total number of measuring points read/write 1~20
4010300 66device addressread/write1~249
4010400 67baud rateread/write0~6
4010500 68communication moderead/write1~4
4010600 69protocol typeread/write1~10

  For example, the range is 0~400, the analog output is 4~20mA current signal, and current The calculation relationship is as shown in the formula: C = (A2-A1) * (X-B1) / (B2-B1) + A1, where A2 is range upper limit, A1 is the lower limit of the range, B2 is current output range upper limit, B1 is the lower limit, X is the currently read value, and C is the calculated current value. The list of commonly used values is as follows:
current(mA)Value () Calculation Process
40.0(400-0)*(4-4)÷(20-4)+0
525.0(400-0)*(5-4)÷(20-4)+0
650.0(400-0)*(6-4)÷(20-4)+0
775.0(400-0)*(7-4)÷(20-4)+0
8100.0(400-0)*(8-4)÷(20-4)+0
9125.0(400-0)*(9-4)÷(20-4)+0
10150.0(400-0)*(10-4)÷(20-4)+0
11175.0(400-0)*(11-4)÷(20-4)+0
12200.0(400-0)*(12-4)÷(20-4)+0
13225.0(400-0)*(13-4)÷(20-4)+0
14250.0(400-0)*(14-4)÷(20-4)+0
15275.0(400-0)*(15-4)÷(20-4)+0
16300.0(400-0)*(16-4)÷(20-4)+0
17325.0(400-0)*(17-4)÷(20-4)+0
18350.0(400-0)*(18-4)÷(20-4)+0
19375.0(400-0)*(19-4)÷(20-4)+0
20400.0(400-0)*(20-4)÷(20-4)+0
    As shown in the above formula, when measuring 8mA, current current is 104。
  For example, the range is 0~400, the analog output is 0~10V DC0-10Vvoltage signal, and DC0-10Vvoltage The calculation relationship is as shown in the formula: C = (A2-A1) * (X-B1) / (B2-B1) + A1, where A2 is range upper limit, A1 is the lower limit of the range, B2 is DC0-10Vvoltage output range upper limit, B1 is the lower limit, X is the currently read value, and C is the calculated DC0-10Vvoltage value. The list of commonly used values is as follows:
DC0-10Vvoltage(V)Value () Calculation Process
00.0(400-0)*(0-0)÷(10-0)+0
140.0(400-0)*(1-0)÷(10-0)+0
280.0(400-0)*(2-0)÷(10-0)+0
3120.0(400-0)*(3-0)÷(10-0)+0
4160.0(400-0)*(4-0)÷(10-0)+0
5200.0(400-0)*(5-0)÷(10-0)+0
6240.0(400-0)*(6-0)÷(10-0)+0
7280.0(400-0)*(7-0)÷(10-0)+0
8320.0(400-0)*(8-0)÷(10-0)+0
9360.0(400-0)*(9-0)÷(10-0)+0
10400.0(400-0)*(10-0)÷(10-0)+0
    As shown in the above formula, when measuring 5V, current DC0-10Vvoltage is 200。